Меню

Главная Каталог Документация Новости Оплата Доставка О компании Контакты

SIPLUS MICROMASTER 440

Обзор

SIPLUS MICROMASTER 440
General technical specifications of the SIPLUS MICROMASTER 440

Ambient temperature range

-10 ... +50 °C

Conformal Coating

Coating of the printed circuit board and the electronic components

Technical specifications

The technical specifications of the standard product apply with the exception of the ambient conditions.



Ambient conditions

Relative atmospheric humidity

5 … 100%,
condensation permissible



Application

The SIPLUS MICROMASTER 440 inverter can be used for a variety of variable-speed drive tasks. Its flexibility makes it suitable for a wide range of applications. This wide range includes cranes and hoisting gear, high-bay warehouses, machines for the food and beverages industry, packaging machines, etc.; i.e. applications that require frequency inverters with higher functionality and higher dynamic response than normal.

The inverter is especially characterized by its customer-oriented performance and ease-of-use. Its large range of line voltages enables it to be used all over the world.

Design

The SIPLUS MICROMASTER 440 inverter has a modular design. The operator panels and modules can be easily exchanged.

Main features
  • Easy, guided commissioning
  • Modular construction allows maximum configuration flexibility
  • 6 programmable isolated digital inputs
  • 2 analog inputs (0 V to 10 V, 0 mA to 20 mA, scalable) can also be used as a 7th/8th digital input
  • 2 programmable analog outputs (0 mA to 20 mA)
  • 3 programmable relay outputs (30 V DC/5 A, resistive load; 250 V AC/2 A, inductive load
  • Low-noise motor operation through high pulse frequencies, adjustable (observe derating if necessary)
  • Protection for motor and inverter
Accessories (overview)
  • EMC filter, class A/B
  • LC filter and sine-wave filter
  • Line commutating reactors
  • Output reactors
  • Shield connection plates
  • Basic Operator Panel (BOP) for parameterizing the inverter
  • Plain-text Advanced Operator Panel (AOP) with multiple-language display
  • Plain-text Asian Advanced Operator Panel (AAOP) with Chinese and English display
  • Plain-text Cyrillic Advanced Operator Panel (CAOP) with Cyrillic, German and English display
  • Communication modules
    • PROFIBUS
    • DeviceNet
    • CANopen
  • Incremental encoder evaluation module
  • PC connection kits
  • Mounting kits for installing the operator panels in control cabinet doors
  • PC commissioning programs under Windows 98/NT/2000/XP Professional
  • TIA integration with Drive ES
International standards
  • The MICROMASTER 440 inverter fulfills the requirements of the EU low-voltage directive
  • The MICROMASTER 440 inverter has CE marking.
  • Certified according to uL and c uL
  • c-tick
Mechanical characteristic data
  • Modular design
  • Operating temperature
    • 0.12 kW to 75 kW: -10 °C to +50 °C (+14 °F to +122 °F)
    • 90 kW to 200 kW: 0 °C to +40 °C (+32 °F to +104 °F)
  • Compact enclosure due to high power density
  • Simple cable connection, separate mains and motor connections for optimum electromagnetic compatibility
  • Plug-in operator panels
  • Screwless control terminal strip on removable I/O board
Performance characteristic data
  • Latest IGBT technology
  • Digital microprocessor control
  • High-quality vector control
  • Flux current control (FCC) for enhanced dynamic response and optimized motor control
  • U/f characteristic linear
  • U/f characteristic quadratic
  • Multipoint characteristic (programmable U/f characteristic)
  • Torque control
  • Flying restart
  • Slip compensation
  • Automatic restart after mains failure or operational fault
  • Free function blocks for logic and arithmetic operations
  • Kinetic buffering
  • Positioning down ramp
  • High-quality internal PID controller for simple process control (autotuning)
  • Programmable ramp-up/ramp-down times 0 s to 650 s
  • Ramp smoothing
  • Fast current limitation (FCL) for uninterrupted operation
  • Fast, reproducible response from the digital inputs
  • Precise setpoint input by means of 2 high-resolution 10-bit analog inputs
  • Compound braking for controlled rapid braking
  • Integrated Braking Module (only for inverters 0.12 kW to 75 kW)
  • 4 skip frequencies
  • Removable "Y" capacitor for use on IT networks (with ungrounded networks the "Y" capacitor must be removed and an output reactor installed)
Protection characteristic data
  • Overload capability
    • CT operation
      0.12 kW to 75 kW:
      overload current 1.5 x  rated output current (i.e. 150% overload capability) for 60 s, cycle time 300 s,
      and 2 x rated output current (i.e. 200% overload capability) for 3 s, cycle time 300 s
      90 kW to 200 kW:
      overload current 1.36 x  rated output current (i.e. 136% overload capability) for 57 s, cycle time 300 s,
      and 1.6 x rated output current (i.e. 160% overload capability) for 3 s, cycle time 300 s
    • VT operation
      5.5 kW to 90 kW:
      overload current 1.4 x  rated output current (i.e. 140% overload capability) for 3 s,
      and 1.1 x rated output current (i.e. 110% overload capability) for 60 s, cycle time 300 s
      110 kW to 250 kW:
      overload current 1.5 x  rated output current (i.e. 150% overload capability) for 1 s,
      and 1.1 x rated output current (i.e. 110% overload capability) for 59 s, cycle time 300 s
  • Overvoltage/undervoltage protection
  • Overtemperature protection for the inverter
  • Special direct connection for PTC or KTY for motor protection
  • Ground-fault protection
  • Short-circuit protection
  • Thermal motor protection I2t
  • Motor blocking protection
  • Stall protection
  • Parameter locking

 

SIPLUS MICROMASTER 440